Relays control circuits through a low-power signal. An electro-magnetic current actuates the relay, creating a closed circuit within the device. General purpose relays are used in applications including HVAC systems, standby power supplies and telephone exchanges. We carry extensive inventory to meet delivery schedules.
- UL File 508 No. E134517
- ROHS Compliant – Environmentally Friendly
- DPDT, DPST-NO switching configurations
- Class F Insulation System
- .250″ QC Terminals
- Multi-Positional Mounting
Coil Voltage | 24 VAC | 120 VAC | 240 VAC | 277 VAC |
DPDT | HCR-12CQ1AA | HCR-12CT1AA | HCR-12CU1AA | HCR-12CV1AA |
DPST-NO | HCR-12AQ1AA | HCR-12AT1AA | HCR-12AU1AA | HCR-12AV1AA |
HCR | - | 1 | 2X | Q | 1 | AA | XXX |
Series | Packaging | Relay Type | Pole Form | Coil Voltage | Contact Rating | Mounting | Custom Identification |
Hartland Controls Relay | (-) Factory Bulk Box (Y) Individual Pack Box | 1 | 2A DPDT 2C DPST | Q 24 VAC T 120 VAC U 208/240 VAC V 277 VAC | 1 Power Duty Rating 2 Pilot Duty | AA 2.350 mtg. ctr. | 000-999 Optional Customer Number assigned by Hartland Controls |
Arrangement
DPDT, DPST-NO
Contact Material
AgCdO
Power Ratings – NO
14 FLA 60 LRA @240 VAC (AC Type)
30 Amps Resistive @ 277 VAC
1 HP @ 120 VAC
Power Ratings – NC
3A @ 277 VAC
Temperature Range
-40 to +65 C
Unit Weight
.19 lb
Power Pole Terminations
.250″ QC
Coil Termination
.250″ QC
Mechanical Life Expectancy
5 million operations
Electrical Life Expectancy
100,000 operations – resistive
Nominal Coil Power
AC 4.0 VA
Coil ID Letter | Nominal Coil Voltage VAC | Pick Up Voltage VAC | Drop Out Voltage VAC | Maximum Coil Voltage VAC | Nominal Coil Resistance Ohms | Sealed VA (maximum) | Inrush VA |
Q | 24 | 20.4 | 4.8 | 26.4 | 77 | 4 | 5 |
T | 120 | 102 | 24 | 132 | 1,800 | 4 | 5 |
U | 208/240 | 176 | 48 | 264 | 7,000 | 4 | 5 |