3 pole contactors are typically used in commercial applications. These contactors utilize three wires to control electrical current direction. Our engineers and quality specialists provide services that meet or exceed customer requirements—all products undergo in-house testing and validation. We carry extensive inventory to meet delivery schedules.
How much do you know about Contactors? Get the free eBook on understanding and choosing the right contactor.
- 3 Pole NO
- Silver Cadmium Oxide Contacts
- UL 508 File NO. E227250
- CSA File No. 221260 (1456104)
FLA Rating | Number of Poles | 24 V Coil | 120V Coil | 208/240V Coil | 277V Coil | 480V Coil |
50 FLA | 3 | HCDY3XQ05CJ | HCDY3XT05CJ | HCDY3XU05CJ | HCDY3XV05CJ | HCDY3XH05CJ |
60 FLA | 3 | HCDY3XQ06CJ | HCDY3XT06CJ | HCDY3XU06CJ | HCDY3XV06CJ | HCDY3XH06CJ |
75 FLA | 3 | HCDY3XQ07JS | HCDY3XT07JS | HCDY3XU07JS | HCDY3XV07JS | HCDY3XH07JS |
90 FLA | 3 | HCDY3XQ09JS | HCDY3XT09JS | HCDY3XU09JS | HCDY3XV09JS | HCDY3XH09JS |
120 FLA | 3 | HCDY3XQ12JS | HCDY3XT12JS | HCDY3XU12JS | HCDY3XV12JS | HCDY3XH12JS |
Initial Dielectric Strength
Between Contacts & Coils: 2,200 VAC
Between Poles: 2,200 VAC
Between Open Contacts: 2,200 VAC
Arc Cover
Standard
Insulation System
130°C Class B
Temperature Range
-40°C to +65°C
-40°F to +150°F
Unit Weight
50–60 FLA 2 lbs
75–120 FLA 4 lbs
Power Pole Terminations
Aluminum box lug
Wire Size
50/60 FLA Box Lug 14-2
75/90 FLA Box Lug 14-1
Recommended Tightening Torque
Box lug: 50 in. lbs
Quick Connects
Coil terminals:
Dual: .250″ QC or #6–32 screw/.250″ QC
Power terminals:
Dual .250″ QC
50–60 FLA Contactors |
Nominal Coil Voltage | 24 | 120 | 208/240 | 277 | 480 |
Nominal Coil Resistance Ohms | 3. | 90 | 302 | 483 | 1453 |
Maximum Pick Up Voltage Minimum Drop Out Voltage | 18 6–15 | 93 20–70 | 177 40–140 | 235 50–165 | 384 150–270 |
Nominal Inrush VA @ 60 Hz Nominal Inrush VA @ 50 Hz | 95.8 102.9 | 105.5 113.4 | 123.1 131.8 | 105.9 112.5 | 110.9 117.5 |
Nominal Sealed VA @ 60 Hz Nominal Sealed VA @ 50 Hz | 8.8 10.9 | 8.7 10.5 | 11.8 14 | 10.9 12.3 | 8.9 10.8 |
Maximum Coil Voltage | 30 | 132 | 264 | 300 | 520 |
75–120 FLA Contactors |
Nominal Coil Voltage | 24 | 120 | 208/240 | 277 | 480 |
Nominal Coil Resistance Ohms | 0.65 | 17 | 52 | 97 | 268 |
Maximum Pick Up Voltage Minimum Drop Out Voltage | 18 6–15 | 88 20–70 | 177 40–110 | 220 65–185 | 384 150–270 |
Nominal Inrush VA @ 60 Hz Nominal Inrush VA @ 50 Hz | 203.9 238.2 | 204.2 241.2 | 246.5 290.7 | 191.4 226.1 | 203 240.4 |
Nominal Sealed VA @ 60 Hz Nominal Sealed VA @ 50 Hz | 19.2 25 | 17.5 21.9 | 23.3 31.2 | 17.5 21.5 | 17.3 22.6 |
Maximum Coil Voltage | 30 | 132 | 264 | 300 | 520 |
Full Load Amps | Resistive Amps @ 600 VAC | Locked Rotor Amps @ 240/277 VAC | Locked Rotor Amps @ 480 VAC | Locked Rotor Amps @ 600 VAC |
3 Pole Contactors | ||||
50 | 65 | 300 | 250 | 200 |
60 | 75 | 360 | 300 | 240 |
75 | 90 | 450 | 375 | 300 |
90 | 120 | 540 | 450 | 360 |
120 | 150 | 720 | 600 | 480 |
Voltage | Single Phase | Three Phase |
3 Pole Contactors | ||
120 240 480 600 | 3 10 - - | - 15 30 30 |
120 240 480 600 | 5 10 - - | - 25 30 30 |
120 240 480 600 | 5 15 - - | - 25 40 40 |
120 240 480 600 | 7.5 20 - - | - 30 50 50 |
120 240 480 600 | 7.5 20 - - | - 30 50 50 |