1 & 2 pole contactors are typically used in residential applications. These contactors utilize one wire to control electrical current direction. Our engineers and quality specialists provide services that meet or exceed customer requirements—all products undergo in-house testing and validation. We carry extensive inventory to meet delivery schedules.
How much do you know about Contactors? Get the free eBook on understanding and choosing the right contactor.
- 1 Pole NO with or without shunt
- 2 Pole NO
- Silver Cadmium Oxide Contacts
- UL 508 File NO. E227250
- Semko/CE File No. EN 60947-4-1:2001
- CSA File No. 221260 (1456104)
FLA Rating | Number of Poles | 24 V Coil | 120V Coil | 208/240V Coil | 277V Coil | 480V Coil |
20 FLA | 1 2 | HCC-1XQ00AA HCC-2XQ00AA | HCC-1XT00AA HCC-2XT00AA | HCC-1XU00AA HCC-2XU00AA | HCC-1XV00AA HCC-2XV00AA | HCC-1XH00AA HCC-2XH00AA |
25 FLA | 1 2 | HCC-1XQ01AA HCC-2XQ01AA | HCC-1XT01AA HCC-2XT01AA | HCC-1XU01AA HCC-2XU01AA | HCC-1XV01AA HCC-2XV01AA | HCC-1XH01AA HCC-2XH01AA |
30 FLA | 1 2 | HCC-1XQ02AA HCC-2XQ02AA | HCC-1XT02AA HCC-2XT02AA | HCC-1XU02AA HCC-2XU02AA | HCC-1XV02AA HCC-2XV02AA | HCC-1XH02AA HCC-2XH02AA |
40 FLA | 1 2 | HCC-1XQ04GG HCC-2XQ04GG | HCC-1XT04GG HCC-2XT04GG | HCC-1XU04GG HCC-2XU04GG | HCC-1XV04GG HCC-2XV04GG | HCC-1XH04GG HCC-2XH04GG |
Initial Dielectric Strength
Between Contacts & Coils: 2,200 VAC
Between Poles: 2,200 VAC (includes shunt)
Between Open Contacts: 2,200 VAC (no shunt)
Arc Cover
Optional on 20 – 30 FLA
Standard on 40 FLA
Insulation System
130°C Class B
Temperature Range
-40°C to +65°C
-40°F to +150°F
Unit Weight
1 Pole .5 lb
2 Pole .6 lb
Power Pole Terminations
#10-32 screw or box lug
Wire Size
#10-32 screw 16-8 (must use ring terminal)
Box lug 14-4
Recommended Tightening Torque
#10-32 screw: 22 in. lbs
Box lug: 40 in. lbs
Quick Connects
Coil terminals:
Dual: .250″ QC
Power terminals:
1 Pole: Quad .250″ QC
2 Pole: Dual or Quad .250″ QC
1 Pole Contactors |
Nominal Coil Voltage | 24 | 120 | 208/240 | 277 | 480 |
Nominal Coil Resistance Ohms | 18 | 420 | 1800 | 2500 | 8000 |
Maximum Pick Up Voltage Minimum Drop Out Voltage | 18 6–15 | 88 20–70 | 177 40–140 | 221 50–165 | 384 150–270 |
Nominal Inrush VA @ 60 Hz Nominal Inrush VA @ 50 Hz | 17.9 19.7 | 22 24.2 | 22.4 24.1 | 21.2 23 | 19.5 21.5 |
Nominal Sealed VA @ 60 Hz Nominal Sealed VA @ 50 Hz | 4.7 6.0 | 7.6 10.1 | 6.6 9.3 | 8.6 10.1 | 4.8 6.6 |
Maximum Coil Voltage | 30 | 132 | 264 | 300 | 520 |
2 Pole Contactors |
Nominal Coil Voltage | 24 | 120 | 208/240 | 277 | 480 |
Nominal Coil Resistance Ohms | 11 | 237 | 1000 | 1600 | 4200 |
Maximum Pick Up Voltage Minimum Drop Out Voltage | 18 6–15 | 88 20–70 | 177 40–140 | 221 50–165 | 384 150–270 |
Nominal Inrush VA @ 60 Hz Nominal Inrush VA @ 50 Hz | 30.5 32.7 | 35.6 39.5 | 35.7 39.3 | 29.2 32.2 | 31.5 35 |
Nominal Sealed VA @ 60 Hz Nominal Sealed VA @ 50 Hz | 7.5 9 | 8.9 10.9 | 8.7 10.9 | 8.8 10.1 | 11.8 12.7 |
Maximum Coil Voltage | 30 | 132 | 264 | 300 | 520 |
Full Load Amps | Resistive Amps @ 600 VAC | Locked Rotor Amps @ 240/277 VAC | Locked Rotor Amps @ 480 VAC | Locked Rotor Amps @ 600 VAC |
1 Pole Contactors | ||||
20 | 30 | 120 | 100 | 80 |
25 | 35 | 150 | 125 | 100 |
30 | 40 | 180 | 150 | 120 |
40 | 50 | 240 | 200 | 160 |
2 Pole Contactors | ||||
20 | 30 | 120 | 100 | 80 |
25 | 35 | 150 | 125 | 100 |
30 | 40 | 180 | 150 | 120 |
40 | 50 | 240 | 200 | 160 |